INSP-Sprinkler Rough-in | 12/18/2019 | 12/19/2019 | 12/19/2019 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping in scope of work complete, scope of work approved for cover.
Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|
INSP-Sprinkler Rough-in | 12/11/2019 | 12/12/2019 | 12/12/2019 | A | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, area of work approved for cover. Quick response heads were used for the new install, remaining open area around scope of work has standard response heads, heads will need to all be standard response or quick response, a resubmittal will be required for approval on type of head to be installed. Will verify head change during final inspection.
Contact: Steve Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|