Description
New fire sprinkler core and shell in existing construction under sloped, exposed, combustible structure. New dry system to protect within and beneath porte cochere. Dry horizontal sidewall sprinklers to protect beneath exterior awning.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro6/23/20206/25/20206/25/2020APASS
DetailsTroy Cobbley
24hr air test and overhead 200lb test on dry system witnessed with no pressure loss.

Phone #: ###-#### Inspection requested via web by jeremiah robison
INSP-Sprinkler Rough-in/Hydro6/23/20206/24/20206/24/2020APART
DetailsTroy Cobbley
Overhead hydro for wet system witnessed. Dry system 24 hour air test started at 8:30 with 51psi on the guage. Plan mods are needed for the changes and inspection started over. Need through bolts for the EQ braces as discussed. Need insulation in the space above the riser room as discussed.

Leon is the contact. it is going to be 24hr air on dry and hydro on wet. Thank you sir Phone #: ###-#### Inspection requested via web by jeremiah robison
INSP-Conference5/4/20205/4/20205/4/2020PDONE
DetailsTroy Cobbley
Mike Martin and I talked about the need for the two dry pendants to be installed in the canopy. Thank you in advance Phone #: ###-#### Inspection requested via web by jeremiah robison