INSP-Final Inspection | 7/1/2020 | 7/7/2020 | 7/7/2020 | A | PASS |
Greg Ruxton
|
|
|
Previously noted synch issues on notification appliances have been resolved. All notification appliances were tested.
Please call 20-30 minutes prior to inspection. You will be meeting technician Jason Petty on site. Phone #: ###-#### Inspection requested via web by jason petty
|
INSP-Final Inspection | 6/12/2020 | 6/17/2020 | 6/17/2020 | A | CANC |
Jim Page
|
|
|
Inspection request cancelled per conversation with point of contact, during pre-test, sync issues were observed, inspection will be rescheduled after sync issue is resloved.
Please call 15-20 minutes prior to arrival. You will be meeting with technician Justin on site. Phone #: ###-#### Inspection requested via web by jason petty
|
INSP-Final Inspection | 6/9/2020 | 6/12/2020 | 6/12/2020 | A | FAIL |
Jim Page
|
|
|
Add device in room, basement level as discussed. Lower 4 devices due to blockage of ceiling soffit, soffit block affect of strobe. Move smoke detector that is too far down from the ceiling as discussed.
Please call 15-20 minutes prior to arrival, you will be meeting Justin Volquardsen on site. Phone #: ###-#### Inspection requested via web by jason petty
|