Permit Information
Permit NumberFIR20-00383
StatusIssued
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 2892 S GREBE PL
Project NameHARRIS RANCH NORTH LOT 72
Customer Number 
ePlanReviewYes
Description
TFSS TO INSTALL A NEW NFPA 13D FIRE SPRINKLER SYSTEM IN THIS NEW SINGLE FAMILY DWELLING.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro6/24/20206/25/20206/25/2020APASS
DetailsTroy Cobbley
Rough/hydro/tenting passed. Piping can be covered. , call Anthony before heading out, he will meet you there with the updated approved plans - will take him 30 minutes to get up there. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro6/17/20206/18/20206/18/2020AFAIL
DetailsTroy Cobbley
Plan mods are needed since 1" piping was installed not the approved 3/4", missing pendant in one room, pipe has been sprayed with foam. Inspection stopped.

Overhead rough/hydro/tenting, call James before heading out! Phone #: ###-#### Inspection requested via web by Anthony Minichiello