INSP-Final Inspection | 7/28/2020 | 7/29/2020 | 7/29/2020 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, hood suppression system activation has been witnessed.
Leo- */Screening*/ *Retirement Center unsure if there is a recent case of COVID but inspector should proceed with caution. Phone #: ###-####
|
INSP-Final Inspection | 7/22/2020 | 7/22/2020 | 7/22/2020 | A | FAIL |
Jim Page
|
|
|
Gas valve indicator light for valve trip during hood suppresion activation does not functioned, will need to be operational before next inspection. Added fryer is not compliant for clearance, fryer needs to be a minimum 6 inches under hood edge to be compliant. Provide splash guard between flat top cooker and fryer.
|
INSP-Alarm Testing | 7/20/2020 | 7/22/2020 | 7/22/2020 | A | CANC |
Jim Page
|
|
|
Inspection was for final inspection, not alarm testing, this request is cancelled and the correct request will be generated.
SCREENED retirement building (could not answer about symtoms or interaction) // Leo Phone #: ###-####
|