Permit NumberFIR20-00432
StatusFinaled
Name JOHNSON CONTROLS FIRE PROTECTION SE
Site Address 739 E PARKCENTER BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
Cooking Hood Fire Extinguishing System: Adding supply line and nozzle to cover new appliance. Existing Ansul R-102 system modification
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/28/20207/29/20207/29/2020APASS
DetailsJim Page
Previously noted items have been corrected, hood suppression system activation has been witnessed.

Leo- */Screening*/ *Retirement Center unsure if there is a recent case of COVID but inspector should proceed with caution. Phone #: ###-####
INSP-Final Inspection7/22/20207/22/20207/22/2020AFAIL
DetailsJim Page
Gas valve indicator light for valve trip during hood suppresion activation does not functioned, will need to be operational before next inspection. Added fryer is not compliant for clearance, fryer needs to be a minimum 6 inches under hood edge to be compliant. Provide splash guard between flat top cooker and fryer.
INSP-Alarm Testing7/20/20207/22/20207/22/2020ACANC
DetailsJim Page
Inspection was for final inspection, not alarm testing, this request is cancelled and the correct request will be generated.

SCREENED retirement building (could not answer about symtoms or interaction) // Leo Phone #: ###-####