GCA-Final | 4/27/2015 | 4/27/2015 | 4/27/2015 | P | PASS |
Daryl DeGrange
|
|
|
corrections completed, final ok
|
GCA-Final | 3/25/2015 | 3/26/2015 | 3/28/2015 | A | FAIL |
Daryl DeGrange
|
|
|
Electrical work performed by non Idaho licenced contractor. Installed 20 amp breaker on 15 amp branch circuit for window A/C unit. Several receptacles in need of maintenance, over heating and lights flickering due to loose stab in wiring receptacle connections. Five working day to start the process to get problem corrected. If not complaint within with in this time Boise City will start Bateman process.
|