GCE-Final | 1/26/2010 | 1/27/2010 | 1/27/2010 | A | CANC |
Doug A Poedy
|
|
|
Contact Hume @ ###-####or Kim @ ###-####. Duplicate request.
|
GCE-Final | 1/26/2010 | 1/27/2010 | 1/27/2010 | A | PASS |
Doug A Poedy
|
|
|
Contact Hume @ ###-####or Kim @ ###-####. Ok final.
|
GCE-Final | 1/12/2010 | 1/13/2010 | 1/13/2010 | A | CANC |
Bob Reichert
|
|
|
Contact Hume @###-#### wrong type request, see p/s
|
GCE-Permanent Service | 1/13/2010 | 1/13/2010 | 1/13/2010 | A | PASS |
Bob Reichert
|
|
|
Contact Hume @###-#### corrections made, p/s o/h n ok, no esc this project
|
GCE-Final | 1/8/2010 | 1/11/2010 | 1/11/2010 | A | FAIL |
Bob Reichert
|
|
|
Contact # ###-####or Tim @ ###-#### called, left correction notice, NEC 250.24(A)(1) gec shall be terminated on terminal to which grounded conductor is terminated, 312.5 all conductors entering enclosure shall have abrasion protection, 250.24(A)(5) load side service disconnect grounded conductor shall not be connected to equipment grounding conductor, 250.96 non-conductive paint shall be removed at contact points, told contractor to ask for p/s inspection, no esc this project
|
GCE-Rough-In | 1/5/2010 | 1/6/2010 | 1/6/2010 | A | PASS |
Bob Reichert
|
|
|
contact Hume @ ###-#### ri ok, will call for service later, no esc this project
|
GCE-Rough-In | 12/31/2009 | 1/4/2010 | 1/4/2010 | A | DONE |
Bob Reichert
|
|
|
Contact Hume @###-#### see response
|
GCE-Rough-In | 12/31/2009 | 1/4/2010 | 1/4/2010 | A | PASS |
Bob Reichert
|
|
|
Contact Hume @###-#### called contractor, ri ok, no esc this project
|