GCE-Final | 6/2/2011 | 6/2/2011 | 6/2/2011 | P | PASS |
Daryl DeGrange
|
|
|
final ok
|
GCE-Permanent Service | 6/1/2011 | 6/2/2011 | 6/2/2011 | A | PASS |
Daryl DeGrange
|
|
|
Permanent ServiceDale @ ###-#### or ###-####Call in advance p/s o/h rec ok
|
GCE-Rough-In Permanent Service | 5/26/2011 | 5/27/2011 | 5/27/2011 | A | FAIL |
Jack Frank
|
|
|
Rough-In/Perm ServiceDale @ ###-#### or ###-####Call in advance talked with owner, correction posted 250.24(A)(1) shall terminate GEC at neutral bus, needs to install green bond screw312.5(C) romex and water bond shall enter p/s panel with a connector note owner needs to post address at site
|
GCE-Rough-In Permanent Service | 5/23/2011 | 5/24/2011 | 5/24/2011 | A | FAIL |
Daryl DeGrange
|
|
|
Rough-In/Perm ServiceDale @ ###-####Call in advance Replace indoor panel installed outdoors with listed rain tight panel. Provide 2-8ft. ground rods 6 ft. apart with contiuous grounding conductor #6 cu. provide water pipe bond #6 cu
|