DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
GCE-Final8/8/20128/9/20128/9/2012APASS
DetailsDaryl DeGrange
(Mandatory Inspection)
###-####
PM inspection requested for today please. final ok
GCE-Final8/8/20128/8/20128/8/2012PCANC
DetailsDoug A Poedy
(Mandatory Inspection)
###-####
PM inspection requested for today please.Rescheduled
GCE-Permanent Service2/24/20122/27/20122/27/2012APASS
DetailsDaryl DeGrange
Todd @ ###-####Call in advance p/s u/g rec ok
GCE-Permanent Service2/23/20122/23/20122/23/2012PNH
DetailsDaryl DeGrange
tim - ###-#### No access to indoor panels
GCE-Permanent Service2/22/20122/23/20122/23/2012AFAIL
DetailsDaryl DeGrange
Tim @ ###-#### service discinnect still not accessible, locked in on position
GCE-Final12/27/201112/28/201112/28/2011ANR
DetailsBob Reichert
Todd @ ###-####Call in advance - AM Inspection see fail p/s
GCE-Permanent Service12/27/201112/28/201112/28/2011AFAIL
DetailsBob Reichert
Todd @ ###-####Call in advance - AM Inspection called, left correction notice, NEC250.56 shall augment grounding electrode with 1 additional rod if less than 25 ohms, BCC shall identify all service disconnects and sub-panels, shall provide access to sub-panels and provide conductors and fuses