GCE-Final | 4/16/2013 | 4/17/2013 | 4/17/2013 | A | PASS |
Rock A. Hudson
|
|
|
(Mandatory Inspection) Greg ###-#### Final ok
|
GCE-Final | 4/15/2013 | 4/16/2013 | 4/16/2013 | P | CANC |
Rock A. Hudson
|
|
|
###-#### Call in advance contractor called to cancel
|
GCE-Final | 3/27/2013 | 3/28/2013 | 3/28/2013 | A | FAIL |
Rock A. Hudson
|
|
|
Erin @ ###-#### Call for access -Exterior and interior emergency lighting not installed as noted on print. -Additional show room outlets required 210.62 -All electrical boxes shall have device covers. - Panel cover not installed. -Bathroom receptical shall be GFCI proteced and secured
|
GCE-Rough-In | 6/12/2012 | 6/13/2012 | 6/13/2012 | A | PASS |
Daryl DeGrange
|
|
|
Greg @ ###-#### rough-in ok cover walls
|
GCE-Rough-In | 6/12/2012 | 6/12/2012 | 6/12/2012 | P | FAIL |
Daryl DeGrange
|
|
|
Greg Phone #: ###-#### NEC.330.12(1) subject physical damage
|