GCE-Final | 10/3/2013 | 10/3/2013 | 10/3/2013 | P | PASS |
Rock A. Hudson
|
|
|
John ###-#### call first Final ok
|
GCE-Rough-In Permanent Service | 6/25/2013 | 6/25/2013 | 6/25/2013 | P | PASS |
Rock A. Hudson
|
|
|
###-#### Rough in ok cover p/s u/g n ok
|
GCE-Rough-In | 6/24/2013 | 6/24/2013 | 6/24/2013 | P | FAIL |
Rock A. Hudson
|
|
|
John ###-#### 250.24(A)(1)- The grounding electode conductor shall connect to the same terminal or bus as the grounded conductor. 314.23(B)(1)- Screws where used as a fastening means shall not pass through box unless protected to avoid abrasion.
|