GCE-Final | 10/18/2013 | 10/21/2013 | 10/21/2013 | A | PASS |
Rock A. Hudson
|
|
|
(Mandatory Inspection)Terry ###-#### Final ok
|
GCE-Final | 10/17/2013 | 10/18/2013 | 10/18/2013 | A | FAIL |
Rock A. Hudson
|
|
|
Terry ###-#### 210.52- 4' wall space in spare bed shall have required receptical outlet. 422.30- A disconnecting means shall be provided for fixed appliances. Built in oven lock-out. *Panel cover shall be completely secured.
|
GCE-Rough-In | 8/20/2013 | 8/21/2013 | 8/21/2013 | A | PASS |
Rock A. Hudson
|
|
|
Terry ###-#### Rough in ok cover p/s u/g n ok
|