GCE-Final | 12/5/2013 | 12/6/2013 | 12/6/2013 | A | PASS |
Rock A. Hudson
|
|
|
Alan ###-#### Final ok
|
GCE-Rough-In | 11/27/2013 | 12/2/2013 | 12/2/2013 | A | PASS |
Rock A. Hudson
|
|
|
Alan ###-#### ceiling grid Rough in ok cover
|
GCE-Rough-In | 11/26/2013 | 11/26/2013 | 11/26/2013 | P | FAIL |
Rock A. Hudson
|
|
|
Alan ###-#### grid ceiling 314.25- Each box shall have cover. 300.11- Boxes and raceways shall be supported independant of ceiling grid. Exits and 1/2 emt in kitchen. 300.11- cables shall not be supported by ceiling grid. Data and stat wires.
|
GCE-Rough-In Permanent Service | 11/8/2013 | 11/12/2013 | 11/12/2013 | A | PASS |
Daryl DeGrange
|
|
|
Alan ###-#### call first p/s u/g n ok
|
GCE-Rough-In | 10/25/2013 | 10/28/2013 | 10/28/2013 | P | PASS |
Rock A. Hudson
|
|
|
Alan ###-#### Wall and soffit rough in ok cover
|