GCE-Final | 12/18/2013 | 12/19/2013 | 12/19/2013 | A | PASS |
Rock A. Hudson
|
|
|
Dominic ###-#### Service final ok
|
GCE-Permanent Service | 12/19/2013 | 12/19/2013 | 12/19/2013 | P | PASS |
Rock A. Hudson
|
|
|
Dominic ###-#### p/s o/h rec ok
|
GCE-Final | 12/17/2013 | 12/17/2013 | 12/17/2013 | P | CANC |
Rock A. Hudson
|
|
|
Dominic ###-#### Needed permenant service inspection
|
GCE-Permanent Service | 12/17/2013 | 12/17/2013 | 12/17/2013 | P | FAIL |
Rock A. Hudson
|
|
|
Dominic ###-#### 300.11- Service shall be solidly secured to pole. 230.54- Overhead service mast shall contain rain tight fittings. 550.10- Power supply shall be fused at rating of attachment cord and plug, 50 amp. 200.6 Grounded conductor larger than #6 shall be identified with white tape at weatherhead, meter, and panel locations. 358.30- EMT service riser shall be secured within 3' of meter base and within 3' of weatherhead.
|