Permit Information
Permit NumberGCE14-00027
StatusIssued
Name Amp Electric
Site Address 406 E 44TH Unit: 13
Project NameELE2014-00027
Customer Number 
ePlanReviewNo
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
GCE-Final2/24/20142/25/20142/25/2014ANR
DetailsDaryl DeGrange
(Mandatory Inspection) Greg ###-#### Not ready for final at this time, correct space number is required,shall back fill trench for final
GCE-Rough-In Permanent Service2/25/20142/25/20142/25/2014PPASS
DetailsDaryl DeGrange
(Mandatory Inspection) Greg ###-#### corrections done, rough-in cover trench p/s u/g rec ok
GCE-Final2/21/20142/21/20142/21/2014PFAIL
DetailsRock A. Hudson
Greg ###-#### 352.46-bushing required for pvc conduit. 300.4-where raceways contain #4 or larger. these conductors shall be protected from abrasion. 300.5-direct burial conductors shall be 18" minimum depth.