Permit Information
Permit NumberGCE14-00103
StatusFinaled
Name Ultimate Electric
Site Address 9635 W TRIBUTARY
Project NameELE2014-00104
Customer Number 
ePlanReviewNo
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
GCE-Final9/3/20149/4/20149/4/2014APASS
DetailsDaryl DeGrange
(Mandatory Inspection) correction done, final ok
GCE-Final9/2/20149/3/20149/3/2014AFAIL
DetailsDaryl DeGrange
Daniel ###-#### NEC 210.8 (A)(2) and (7) All 15 and 20 ampere 120 volt receptacles located in garages and receptacles located within 6ft. of an sink (laundry room) require GFCI protection.
GCE-Rough-In Permanent Service7/9/20147/9/20147/9/2014PPASS
DetailsRock A. Hudson
Address corrected. Rough in ok cover p/s u/g n ok
GCE-Rough-In Permanent Service7/9/20147/9/20147/9/2014PPASS
DetailsRock A. Hudson
Daniel ###-#### re-inspect from 7.7.2014 inspection Address 9591 shown as on permit GCE14-00102 and GCE14-00103. Garden City office is working to correct address for GCE14-00103 to 9635 Tributary Rough in ok cover p/s u/g n ok
GCE-Rough-In Permanent Service7/7/20147/7/20147/7/2014PFAIL
DetailsRock A. Hudson
Daniel ###-#### 110.27(A)- Panel board live parts shall be guarded against accidental contact.
300.4- NM cable shall be protected from physical damage where bored hole thru framing member does not maintain 1 1/4" from framing surface. Left of fire place, and where ran thru lower plate to crawl through shallow hole.
314.25- All boxes shall have covers. Can by utility.
334.30 NM cable shall be supported with in 4 1/2' of upper plate. 4 way by court yard. Oven NM cable shall be secured with in 12" of box.