GCE-Final | 9/3/2014 | 9/4/2014 | 9/4/2014 | A | PASS |
Daryl DeGrange
|
|
|
(Mandatory Inspection) correction done, final ok
|
GCE-Final | 9/2/2014 | 9/3/2014 | 9/3/2014 | A | FAIL |
Daryl DeGrange
|
|
|
Daniel ###-#### NEC 210.8 (A)(2) and (7) All 15 and 20 ampere 120 volt receptacles located in garages and receptacles located within 6ft. of an sink (laundry room) require GFCI protection.
|
GCE-Rough-In Permanent Service | 7/9/2014 | 7/9/2014 | 7/9/2014 | P | PASS |
Rock A. Hudson
|
|
|
Address corrected. Rough in ok cover p/s u/g n ok
|
GCE-Rough-In Permanent Service | 7/9/2014 | 7/9/2014 | 7/9/2014 | P | PASS |
Rock A. Hudson
|
|
|
Daniel ###-#### re-inspect from 7.7.2014 inspection Address 9591 shown as on permit GCE14-00102 and GCE14-00103. Garden City office is working to correct address for GCE14-00103 to 9635 Tributary Rough in ok cover p/s u/g n ok
|
GCE-Rough-In Permanent Service | 7/7/2014 | 7/7/2014 | 7/7/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Daniel ###-#### 110.27(A)- Panel board live parts shall be guarded against accidental contact. 300.4- NM cable shall be protected from physical damage where bored hole thru framing member does not maintain 1 1/4" from framing surface. Left of fire place, and where ran thru lower plate to crawl through shallow hole. 314.25- All boxes shall have covers. Can by utility. 334.30 NM cable shall be supported with in 4 1/2' of upper plate. 4 way by court yard. Oven NM cable shall be secured with in 12" of box.
|