GCE-Final | 8/27/2014 | 8/27/2014 | 8/27/2014 | P | PASS |
Daryl DeGrange
|
|
|
Rick ###-#### (Mandatory Inspection) final ok duplex
|
GCE-Rough-In Permanent Service | 7/21/2014 | 7/22/2014 | 7/22/2014 | A | PASS |
Rex Boyles
|
|
|
Rick ###-#### r/i ok p/s o/h n ok 2 units 313 and 315 39th st
|
GCE-Rough-In Permanent Service | 7/21/2014 | 7/21/2014 | 7/21/2014 | P | FAIL |
Rex Boyles
|
|
|
Rick ###-#### Install nema 3R listed KO seal in top of meter main, identify meters with addresses with permanent label, Unit 315 needs protection for NM cable within 6foot of attic access.
|
GCE-Rough-In Permanent Service | 7/15/2014 | 7/16/2014 | 7/16/2014 | A | FAIL |
Daryl DeGrange
|
|
|
Rick ###-#### NEC 230.6(5) Unfused service conductor shall not be installed inside building or structure. NEC 320.23 Attic access guard strips, all conductors within 6 ft.
|
GCE-Rough-In Permanent Service | 7/14/2014 | 7/14/2014 | 7/14/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Rick ###-#### 250.148- Any equiptment grounding conductor shall be connected with in box. 334.30 Flat cables shall not be stapled on edge. 406.4 Receptical outlets shall be securely fastened in place.
|