GCE-Final | 8/19/2014 | 8/20/2014 | 8/20/2014 | A | PASS |
Rock A. Hudson
|
|
|
Mike ###-#### Paper permit shows correct address. Final ok
|
GCE-Rough-In | 8/18/2014 | 8/19/2014 | 8/19/2014 | A | PASS |
Daryl DeGrange
|
|
|
Mike ###-#### correction done rough-in ok cover ceiling grid
|
GCE-Rough-In | 8/15/2014 | 8/18/2014 | 8/18/2014 | P | FAIL |
Bob Reichert
|
|
|
mike ###-#### met contractor, left correction notice, BCC shall correct address, NEC 210.62 shall add showroom outlets, 300.11 shall provide seismic wires, 358.30 shall strap emt within 3' of box, NOTE gave ok for border tile only
|
GCE-Rough-In | 7/29/2014 | 7/30/2014 | 7/30/2014 | A | PASS |
Rock A. Hudson
|
|
|
###-#### Final ok
|