GCE-Final | 2/4/2015 | 2/5/2015 | 2/5/2015 | A | FAIL |
Cevyn Recla
|
|
|
Alan ###-#### (B) Disconnecting Means. Each multiwire branch circuit shall be provided with a means that will simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates 408.4 every circuit shall be legibly identified 210.5 C ungrounded conductors shall be permanently identified 314.17 Conductors entering boxes shall be protected, wire entering service with no connector
|
GCE-Permanent Service | 2/3/2015 | 2/4/2015 | 2/4/2015 | A | PASS |
Rex Boyles
|
|
|
Alan ###-#### p/s u/g rec ok
|