GCE-Permanent Service | 5/6/2015 | 5/7/2015 | 5/8/2015 | A | PASS |
Rex Boyles
|
|
|
Jim ###-#### p/s o/h rec ok
|
GCE-Final | 5/6/2015 | 5/7/2015 | 5/7/2015 | A | PASS |
Rex Boyles
|
|
|
Jim ###-#### final ok
|
GCE-Final | 5/6/2015 | 5/6/2015 | 5/6/2015 | P | CANC |
Rex Boyles
|
|
|
Jim ###-#### needed p/s and final inspection type inspections
|
GCE-Permanent Service | 3/31/2015 | 4/3/2015 | 4/3/2015 | A | FAIL |
Rex Boyles
|
|
|
Brian ###-#### Add supplemental ground rod, add intersystem ground bar, #12 conductors tapped off 1oo amp breaker feeding 2 underground conduits without overcurrent protection, overhead feeders to mobile home have no strain releif and don't meet clearances, lots of debris in old meter main and no dead front on meter main.
|