GCE-Final | 9/21/2015 | 9/21/2015 | 9/21/2015 | P | PASS |
Rex Boyles
|
|
|
Lewis ###-#### corrections made final ok
|
GCE-Final | 9/18/2015 | 9/18/2015 | 9/18/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Lewis ###-#### 110.24- Available fault current shall be posted and date value was calculated. 230.70- Main disconnect shall be identified as to its purpose. 330.30- MC cable shall be secured with in 12" of back exit sign. 406.6- Replace broken receptacle plate west wall. 408.4- Circuit directory shall be completed on new panel. 408.7- Existing panels, unused openings shall be closed.
|
GCE-Rough-In | 7/1/2015 | 7/1/2015 | 7/1/2015 | P | PASS |
Eric Story
|
|
|
Louis ###-#### - code: 0478 walls and office cieling rough-in ok cover
|
GCE-Permanent Service | 6/25/2015 | 6/29/2015 | 6/29/2015 | A | NR |
Rex Boyles
|
|
|
Louis ###-#### Idaho Power cancelled appt.
|
GCE-Permanent Service | 6/23/2015 | 6/25/2015 | 6/25/2015 | A | PASS |
Rex Boyles
|
|
|
Contractor ###-#### met with Lewis and confirmed existing water bond for existing service. Existing service being altered on saturday to accomadate new 400 amp meter and main disconnect for T.I.. Power needs to be turned back on saturday for other tenants in building. Will look for available fault current label and ground rods on Monday 6-29-15. p/s u/g rec ok
|
GCE-Rough-In | 6/22/2015 | 6/25/2015 | 6/24/2015 | A | CANC |
Rex Boyles
|
|
|
Contractor ###-####
|