GCE-Final | 1/26/2016 | 1/26/2016 | 1/26/2016 | P | PASS |
Rex Boyles
|
|
|
Bob ###-#### corrections made final ok perm. occ. ok
|
GCE-Final | 1/25/2016 | 1/26/2016 | 1/26/2016 | A | FAIL |
Rex Boyles
|
|
|
Bob ###-#### 210.8(B)(5)-GFCI protection required for receptacles within 6 foot of sinks, Correct fuses for rooftop condensing units, blank plates needed.
|
GCE-Final | 1/13/2016 | 1/14/2016 | 1/14/2016 | A | PART |
Rex Boyles
|
|
|
Bob ###-#### - final for temp. occupancy of main floor partial final ok for 1st floor in highlighted area on plans. Temporary Occupancy ok for 1st floor
|
GCE-Rough-In | 1/12/2016 | 1/12/2016 | 1/12/2016 | P | PASS |
Rex Boyles
|
|
|
Bob ###-#### - partial rough-in r/i t grid ceiings 1st and 2nd floors ok
|
GCE-Rough-In | 1/6/2016 | 1/7/2016 | 1/7/2016 | A | PASS |
Eric Story
|
|
|
Bob ###-#### - partial rough-in back wall outlets ok cover
|
GCE-Rough-In | 1/5/2016 | 1/6/2016 | 1/6/2016 | A | PASS |
Eric Story
|
|
|
Bob ###-#### - partial rough-in upstairs hall hard lid ok cover
|
GCE-Rough-In | 12/29/2015 | 12/29/2015 | 12/29/2015 | P | PASS |
Rex Boyles
|
|
|
Bob ###-#### all hard lid ceilings 1st floor ok to cover
|
GCE-Rough-In | 12/18/2015 | 12/18/2015 | 12/18/2015 | P | PASS |
Rex Boyles
|
|
|
Bob ###-#### - partial rough-in r/i ok wine tasting room walls and switch at bottom of stairs in same area
|
GCE-Rough-In | 12/15/2015 | 12/15/2015 | 12/15/2015 | P | PASS |
Rex Boyles
|
|
|
Bob ###-#### - partial rough-in r/i ok walls in lab. ,bathroom and rear pocket door wall inside and outside. Not necessary to seal penetrations in 50 degree storage rooms. No condensation issues that I can see
|
GCE-Rough-In | 12/14/2015 | 12/14/2015 | 12/14/2015 | P | PASS |
Rex Boyles
|
|
|
Bob ###-#### - partial rough-in r/i lab walls ok
|
GCE-Permanent Service | 12/13/2015 | 12/14/2015 | 12/14/2015 | A | PASS |
Rex Boyles
|
|
|
Bob ###-#### correction made p/s u/g n ok
|
GCE-Permanent Service | 12/9/2015 | 12/10/2015 | 12/10/2015 | A | FAIL |
Bob Reichert
|
|
|
Bob ###-#### met contractor, told to use other method wiring out of floor
|
GCE-Permanent Service | 12/9/2015 | 12/9/2015 | 12/9/2015 | P | FAIL |
Rex Boyles
|
|
|
Bob ###-#### still need fire sprinkeler riser bonded and available fault current info label
|
GCE-Rough-In | 12/9/2015 | 12/9/2015 | 12/9/2015 | P | PASS |
Rex Boyles
|
|
|
Bob ###-#### r/i walls ok upst. offices and corridor see sheet A2.1 pink highlighted areas
|
GCE-Rough-In | 12/1/2015 | 12/1/2015 | 12/1/2015 | P | PASS |
Rex Boyles
|
|
|
Bob ###-#### r/i ok walls highlighted in pink on sheet A2.1
|
GCE-Rough-In | 11/24/2015 | 11/25/2015 | 11/25/2015 | P | PASS |
Eric Story
|
|
|
Bob ###-#### exterior and interior walls as per contractors print ok cover
|
GCE-Rough-In | 9/22/2015 | 9/22/2015 | 9/22/2015 | P | PASS |
Bob Reichert
|
|
|
Bob ###-#### - partial rough-in ok cover u/g north slab
|
GCE-Rough-In | 9/21/2015 | 9/21/2015 | 9/21/2015 | P | PASS |
Rex Boyles
|
|
|
Bob ###-#### r/i ok under slab conduits south lower slab
|
GCE-Rough-In | 8/7/2015 | 8/7/2015 | 8/7/2015 | P | PASS |
Eric Story
|
|
|
Bob ###-#### ufer ok cover
|
GCE-Rough-In | 7/16/2015 | 7/16/2015 | 7/16/2015 | P | PART |
Bob Reichert
|
|
|
Bob ###-#### looked at u/g from xfmr to building foundation, told general we don't usually look at serving utility raceways, 2 90's installed, will see rest later
|