GCE-Final | 2/9/2016 | 2/9/2016 | 2/9/2016 | P | PASS |
Eric Story
|
|
|
Darren ###-#### corrections fixed final ok
|
GCE-Final | 2/3/2016 | 2/4/2016 | 2/4/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Darrin ###-#### 300.15- Furnace splice or termination shall be in a box. 314.20- Where box is installed in a combustible material it shall be flush or extension ring shall be installed to make flush. Boxes in wood trim. 334.12(B)- NM Caable where ran exposed shall be protected from physical damage. Furnace. 440.14- A disconnecting means shall be provided for furnace.
|
GCE-Rough-In | 10/14/2015 | 10/14/2015 | 10/14/2015 | P | PASS |
Eric Story
|
|
|
Dan ###-#### rough-in ok cover p/s u/g n ok
|