GCE-Final | 6/8/2016 | 6/8/2016 | 6/8/2016 | P | PASS |
James Ady
|
|
|
Brandon ###-#### Final ok
|
GCE-Final | 6/7/2016 | 6/8/2016 | 6/8/2016 | A | FAIL |
James Ady
|
|
|
Brandon ###-#### 250.8 A 6 GFCI Protection required in kitchen
|
GCE-Rough-In Permanent Service | 12/9/2015 | 12/8/2015 | 12/10/2015 | P | PASS |
Rex Boyles
|
|
|
Brandon ###-#### corrections made r/i ok p/s u/g n ok
|
GCE-Rough-In Permanent Service | 12/4/2015 | 12/7/2015 | 12/7/2015 | P | FAIL |
Rex Boyles
|
|
|
Brandon ###-#### 310.15(B)(7)- #2 alum ser only rated for 75 amps.80 amp breaker ok as per 240.4(B) 300.4(A)(1)- nailplates needed above sub panel. Load calcs recommended for sub panel
|