GCE-Final | 4/14/2016 | 4/14/2016 | 4/14/2016 | P | PASS |
Rex Boyles
|
|
|
Brandon ###-#### - call for access corrections made final ok
|
GCE-Final | 3/17/2016 | 3/18/2016 | 3/18/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Brandon ###-#### 110.22- AC disconnect shall be identified as to which unit it supplys. 210.8- All 120 volt 15 or 20 amp receptacle outlets installed with in 6' of a sink shall have GFCI protection. 410.16- Incondescent and LED luminaires shall have a minimum of 12" shelf clearance.
|
GCE-Rough-In Permanent Service | 12/9/2015 | 12/8/2015 | 12/10/2015 | P | PASS |
Rex Boyles
|
|
|
Brandon ###-#### corrections made r/i ok p/s u/g n ok
|
GCE-Rough-In Permanent Service | 12/4/2015 | 12/7/2015 | 12/7/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Brandon ###-#### 310.15(B)(7)- #2 SER will be surrounded by thermal insulation, 60 degree column shall be used either change to #1 SER or fuse down to 80 amp max. 314.25- All boxes shall have covers. Can on front of garage cover not installed properly.
|