GCE-Final | 5/6/2016 | 5/9/2016 | 5/9/2016 | A | PASS |
Rex Boyles
|
|
|
Brandon ###-#### final ok
|
GCE-Rough-In Permanent Service | 12/9/2015 | 12/8/2015 | 12/10/2015 | P | PASS |
Rex Boyles
|
|
|
Brandon ###-#### corrections made r/i ok p/s u/g n ok
|
GCE-Rough-In Permanent Service | 12/4/2015 | 12/7/2015 | 12/7/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Brandon ###-#### 110.12(B)- Wiring shall not be damaged. Range wire split above box. repair or replace. 310.15(B)(7)- #2 SER will be surrounded by thermal insulation, 60 degree column shall be used. Either change to #1 SER or fuse down to 80 amp max. 334.30- Max span for support of NM cable shall not exceed 4 1/2'. 10-3 on 2nd floor.
|