Permit Information
Permit NumberMEC05-00408
StatusFinaled
Name TVR INC
Site Address 3110 S BOWN WAY
Project NameBOWN CROSSING MARKET PLACE
Customer Number 
ePlanReview 
Description
RTV'S, Ductwork, Exhaust, GRD's, Hoods JRR 2-4-05
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/30/20056/30/20057/1/2005PPASS
DetailsTroy James
Final; Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen
Final6/27/20056/29/20056/29/2005AFAIL
DetailsTroy James
Final Inspection - Daryl ; Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen need grease receptor to fan on roof
Rough-in6/20/20056/20/20056/21/2005PFAIL
DetailsTroy James
Attn: Daryl; Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen
need required clearances on roof for rtu's and exhausts, called Dave to schedule a meeting
Conference6/21/20056/21/20056/21/2005PDONE
DetailsTroy James
met with TVR in regards to clearance requirements on roof
Rough-in6/9/20056/9/20056/9/2005PPART
DetailsTroy James
ok to cover
Rough-in6/9/20056/9/20056/9/2005PPART
DetailsTroy James
ok to cover
Rough-in6/9/20056/9/20056/9/2005PPART
DetailsTroy James
ok to cover
Rough-in6/9/20056/9/20056/9/2005PPART
DetailsTroy James
ok to cover
Rough-in6/7/20056/8/20056/8/2005AFAIL
DetailsTroy James
Cover inspection; Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen need approval hood listed for one exhaust tap, gas line to be medium pressure to ansul valve, remove flex from make-up air above hood.
Rough-in5/19/20055/20/20055/20/2005APART
DetailsTroy James
Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen, ok to wrap grease duct only
Rough-in5/17/20055/18/20055/18/2005AFAIL
DetailsTroy James
Dave Tully; Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen
grease duct to slope to hood, need hood design and calcs by engineer, make up air design, ok to duct wrap grease duct at floors above
Rough-in5/6/20055/6/20055/6/2005PPART
DetailsTroy James
Dave tully; Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen ok to cover walls and hard lid ceiling only
Rough-in4/26/20054/27/20054/27/2005AFAIL
DetailsTroy James
Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen
c/n posted, inspection for hard lid ceiling and walls only 4/27/2005 11:14:30 AM