Final | 5/10/2005 | 5/11/2005 | 5/11/2005 | A | PASS |
Dixie Fellows
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa...ALL CORRECTIONS DONE...SIGNED CARD
|
Final | 5/9/2005 | 5/10/2005 | 5/10/2005 | A | FAIL |
Dixie Fellows
|
|
|
don; Phone #: ###-#### Internet Inspection Request from: Barbara Moore...screws to be in duct not structure...remove fire caulking from angles
|
Conference | 4/26/2005 | 4/26/2005 | 4/26/2005 | A | PASS |
Dixie Fellows
|
|
|
discussed s/f dampers installed wrong..economizers installed by wed 4/26/2005 11:31:06 AM
|
Final | 3/31/2005 | 3/31/2005 | 3/31/2005 | P | PART |
Alan Hauser
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore all ok except need air balance report on hoods and front part of business that got covered without inspection temporary occ. ok 3/31/2005 5:02:42 PM
|
Rough-in | 3/29/2005 | 3/30/2005 | 3/30/2005 | A | PASS |
Alan Hauser
|
|
|
ran out of time, do wed. am grease ducts ok, ok to wrap 3/30/2005 10:28:23 AM
|
Pressure Test | 3/28/2005 | 3/29/2005 | 3/29/2005 | A | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 3/28/2005 at 6:21:45 PM. Contact: ###-####.
|
Rough-in | 3/29/2005 | 3/29/2005 | 3/29/2005 | P | PASS |
Alan Hauser
|
|
|
all grease ducts redone and smooth interiors, ok to wrap 3/30/2005 10:17:45 AM
|
Rough-in | 3/24/2005 | 3/25/2005 | 3/25/2005 | A | FAIL |
Dixie Fellows
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie inside of grease duct is still full of burrs and lips...met with randy and went over it with him 3/25/2005 9:08:49 AM
|
Rough-in | 3/24/2005 | 3/24/2005 | 3/24/2005 | P | NR |
Dixie Fellows
|
|
|
Don; Phone #: ###-#### Internet Inspection Request from: Jan Rice
|
Rough-in | 3/22/2005 | 3/22/2005 | 3/22/2005 | P | FAIL |
Dixie Fellows
|
|
|
grease duct installation--don; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie inside of grease duct is full of burrs and jagged edges 3/22/2005 4:23:11 PM
|
Conference | 3/16/2005 | 3/16/2005 | 3/16/2005 | P | PASS |
Dixie Fellows
|
|
|
don; Phone #: ###-#### Internet Inspection Request from: Barbara Moore discussed issues 3/16/2005 4:18:11 PM
|
Conference | 3/15/2005 | 3/15/2005 | 3/15/2005 | P | PASS |
Dixie Fellows
|
|
|
randy MET WITH CONTRACTOR..NEED TO HAVE A CONFERENCE WITH ENGINEER 3/15/2005 5:05:42 PM
|