Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberMEC05-00990
StatusFinaled
Name TML LLC
Site Address 4601 S SURPRISE WAY
Project NameTRINITY PRESBYTERIAN CHURCH
Customer Number7698
ePlanReview 
Description
Furnish & install (16) packaged gas/electrical units with isolation roof curbs, furnish & install (2) pad mounted heating/cooling units, registers, grills, diffusers, dampers & fire dampers, F/I (8) roof mounted exhaust fans, all with related duct work with an initial cert of value $252,245///3/29/05 BAS ///final cert of value is $253,201//10/14/05 LEG
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/2/20059/2/20059/2/2005APASS
DetailsBill VanDegrift
final ok
Final8/31/20059/1/20059/1/2005AFAIL
DetailsTroy James
need air ballance report for kitchen
Final8/31/20058/31/20058/31/2005PCANC
DetailsTroy James
Scheduled by a contractor via Hello! on 8/31/2005 at 9:12:14 AM. Contact: ###-####. rescheduled for morning
Final8/18/20058/19/20058/19/2005PFAIL
DetailsTroy James
Scheduled by a contractor via Hello! on 8/18/2005 at 12:32:08 PM. Contact: ###-####.
c/n posted in esi trailer
Final6/29/20057/5/20057/5/2005PFAIL
DetailsTroy James
Scheduled by a contractor via Hello! on 6/29/2005 at 10:49:13 AM. Contact: ###-####. need non-combustible material around type 1 hood at wall, vapor exhuast fan exten 2' above intake at rtu, seal grease hood at curb, need hinged at fan housing and grease receptor, smoke detector installed at units 1,2, and 9
Rough-in6/29/20057/5/20057/5/2005PPASS
DetailsTroy James
Scheduled by a contractor via Hello! on 6/29/2005 at 10:48:17 AM. Contact: ###-####.
Rough-in6/3/20056/6/20056/6/2005PFAIL
DetailsTroy James
Scheduled by a contractor via Hello! on 6/3/2005 at 1:04:06 PM. Contact: ###-####. electricians drilled through grease duct, exhaust fan curb need 18" from roof

Rough-in5/24/20055/25/20055/25/2005APART
DetailsTroy James
Scheduled by a contractor via Hello! on 5/24/2005 at 12:15:26 PM. Contact: ###-####. NOTE: call Mario 1/2 hr prior to inspection ok tocover hard lid ceiling
Rough-in4/27/20054/29/20054/29/2005AFAIL
DetailsTroy James
Scheduled by a contractor via Hello! on 4/27/2005 at 9:12:52 AM. Contact: ###-####. need ceiling f/d at strorage room, ok duct at west wing 4/29/2005 11:08:07 AM