Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberMEC05-02953
StatusFinaled
Name OWYHEE SHEET METAL
Site Address 3200 W CASSIA ST
Project Name 
Customer Number 
ePlanReview 
Description
9/14/2005 - 2 roof top units (A/C & Heater) and 9 furnances for HVAC - $247,495.00 per initial cert of value - cmc ///Final cert of value is $255,745//3/22/06 LEG
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
MEC-Aging Inspection5/23/20065/23/20065/24/2006 PASS
DetailsTroy James
job finaled
Final5/24/20065/24/20065/24/2006PPASS
DetailsTroy James
Final3/22/20063/23/20063/23/2006APART
DetailsLee Rice
gary Note: 1 hr prior inspection; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
Final3/15/20063/17/20063/17/2006AFAIL
DetailsTroy James
please call 1 hr prior to meet//Owyhee Sheet Metal Office; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
need access doors at wall, to access f/d in ceiling, units at east side need access doors to f/d in duct as well
MEC-Aging Inspection2/20/20062/20/20062/22/2006 PEND
DetailsTroy James
wip
MEC-Aging Inspection12/19/200512/19/200512/19/2005 CANC
DetailsTroy James
wip
Conference10/17/200510/17/200510/17/2005PDONE
DetailsTroy James
meet roger at 1:00pm
met with roger eng. INC and owhee sheetmetal, open return plenum in crawl to be used per existing condition, all penetration through ceiling to be f/d or f/s dampers
Pressure Test10/10/200510/11/200510/11/2005APASS
DetailsTroy James
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
Final10/10/200510/10/200510/10/2005ACANC
DetailsTroy James
Conference10/10/200510/10/200510/10/2005ADONE
DetailsTroy James
f/d's required at all ceiling penatrations, need installation instructions for all fire and fire/smoke dampers, install ducted return air plenums, so gas line does not run in return air plenum
Pressure Test10/5/200510/7/200510/7/2005PFAIL
DetailsTroy James
###-#### - kATHY
factory approved gas piping required underground