Final | 1/2/2006 | 1/2/2006 | 1/3/2006 | P | PASS |
Alan Hauser
|
|
|
Ready for final inspection - pls call for garage access code. THANKS!; Phone #: ###-#### Internet Inspection Request from: DeAnna Barrett
|
Rough-in | 9/21/2005 | 9/22/2005 | 9/22/2005 | A | PASS |
Troy James
|
|
|
Phone #: ###-#### Internet Inspection Request from: DeAnna Barrett
|
Pressure Test | 9/20/2005 | 9/21/2005 | 9/21/2005 | A | PASS |
Jim Johnson
|
|
|
Phone #: ###-#### Internet Inspection Request from: DeAnna Barrett
|
Rough-in | 9/20/2005 | 9/21/2005 | 9/21/2005 | A | FAIL |
Jim Johnson
|
|
|
Phone #: ###-#### Internet Inspection Request from: DeAnna Barrett clothes dryer exhaust duct to long ( shall not exceed 25 feet ) need to repipe need to support pvc condensate drains every 4 feet horizontal and every 10 feet vertical as per table m2101.9 IRC 2003
|