Final | 10/23/2007 | 10/24/2007 | 10/24/2007 | A | PASS |
Alan Hauser
|
|
|
|
Rough-in | 10/8/2007 | 10/9/2007 | 10/9/2007 | A | PASS |
Alan Hauser
|
|
|
|
Rough-in | 10/8/2007 | 10/8/2007 | 10/9/2007 | P | PASS |
Alan Hauser
|
|
|
|
Rough-in | 9/6/2007 | 9/7/2007 | 9/7/2007 | A | PART |
Alan Hauser
|
|
|
temp occ for 4th and 5th floor
|
Rough-in | 7/24/2007 | 7/25/2007 | 7/25/2007 | A | NR |
Alan Hauser
|
|
|
KEN CELL ###-#### ROUGH-IN ON THE 2ND FLOOR NORTH AND SOTUH SIDE Phone #: ###-#### Internet Inspection Request from: AMANDA ROBINSON
|
Final | 7/24/2007 | 7/25/2007 | 7/25/2007 | A | PART |
Alan Hauser
|
|
|
Final 1, 2 & 3rd floors only please signed temp. occ. on card, waiting for fire inspectors to get done testing all dampers
|
Rough-in | 7/23/2007 | 7/25/2007 | 7/24/2007 | A | FAIL |
Alan Hauser
|
|
|
correction notice posted with general contractor, contact rita or barbara at city of boise. obtain all permits that are required for work done at this address.
|
Rough-in | 7/20/2007 | 7/23/2007 | 7/23/2007 | A | NR |
Alan Hauser
|
|
|
FINAL OUT 1ST 2ND 3RD FLOORS ONLY KEN CELL ###-#### , will sign final for these floors after fire inspector has signed off on operation of all smoke and smoke/fire dampers. also need to hear from rita deyoung to see if fees are paid.
|
MEC-Aging Inspection | 7/12/2007 | 7/12/2007 | 7/16/2007 | | CANC |
Alan Hauser
|
|
|
|
MEC-Aging Inspection | 5/7/2007 | 5/7/2007 | 5/7/2007 | | CANC |
Alan Hauser
|
|
|
|
Rough-in | 3/2/2007 | 3/7/2007 | 3/7/2007 | A | FAIL |
Alan Hauser
|
|
|
3rd floor, no angles at s/f dampers and some dampers are not straight with wall and operater is in wall
|
Rough-in | 2/21/2007 | 2/28/2007 | 2/28/2007 | A | CANC |
Alan Hauser
|
|
|
|
Rough-in | 2/14/2007 | 2/21/2007 | 2/21/2007 | A | PART |
Alan Hauser
|
|
|
|
Rough-in | 2/9/2007 | 2/14/2007 | 2/14/2007 | A | CANC |
Troy James
|
|
|
Please contact job foreman, Ken Sereduk - ###-####. Phone #: ###-#### called Ken and he will reschedule for next week
|
Rough-in | 2/1/2007 | 2/7/2007 | 2/7/2007 | A | PART |
Alan Hauser
|
|
|
Please contact job foreman, Ken Sereduk - ###-####. Phone #: ###-####
|
Rough-in | 1/18/2007 | 1/24/2007 | 1/24/2007 | A | PEND |
Dixie Fellows
|
|
|
Please contact job foreman, Ken Sereduk - ###-####. Phone #: ###-####..called ken and he will reschedule when alan gets back..ken said this wont be holding up job
|
Rough-in | 1/9/2007 | 1/10/2007 | 1/10/2007 | A | PART |
Alan Hauser
|
|
|
walked building from 10th down, no areas ready for tile
|
Rough-in | 1/2/2007 | 1/3/2007 | 1/4/2007 | A | PART |
Alan Hauser
|
|
|
Please contact job foreman, Ken Sereduk - ###-####. Internet Inspection Request from: RaChelle Meister
|
Rough-in | 12/26/2006 | 12/27/2006 | 12/27/2006 | A | PEND |
Dixie Fellows
|
|
|
Please contact job foreman, Ken Sereduk - ###-#### Internet Inspection Request from: RaChelle Meister..called ken and he requested the inspection wail until alan returns next week...dixie
|
Rough-in | 12/19/2006 | 12/20/2006 | 12/20/2006 | A | PART |
Alan Hauser
|
|
|
Please contact job foreman, Ken Sereduk - ###-####. Internet Inspection Request from: RaChelle Meister
|
Rough-in | 12/20/2006 | 12/20/2006 | 12/20/2006 | P | PART |
Alan Hauser
|
|
|
Please contact job foreman, Ken Sereduk - ###-####. Internet Inspection Request from: RaChelle Meister
|
Rough-in | 12/11/2006 | 12/13/2006 | 12/13/2006 | A | PART |
Alan Hauser
|
|
|
Please contact job foreman, Ken Sereduk - ###-####. Internet Inspection Request from: RaChelle Meister
|
Rough-in | 12/6/2006 | 12/7/2006 | 12/7/2006 | A | PART |
Alan Hauser
|
|
|
Please contact job foreman, Ken Sereduk - ###-####. Internet Inspection Request from: RaChelle Meister
|
Rough-in | 12/4/2006 | 12/6/2006 | 12/6/2006 | A | PEND |
Dixie Fellows
|
|
|
Please contact job foreman, Ken Sereduk - ###-####. Internet Inspection Request from: RaChelle Meister..called ken and he said the inspection could wait until alan could come out as he is familiar with the job..they will reschedule for thurs..thanks dixie
|
Rough-in | 11/30/2006 | 11/30/2006 | 11/30/2006 | A | PART |
Alan Hauser
|
|
|
area in basement ok for cover, fire place flues ok
|
Rough-in | 11/21/2006 | 11/22/2006 | 11/22/2006 | A | PART |
Alan Hauser
|
|
|
Please contact job forman, Ken Sereduk - ###-####. Internet Inspection Request from: RaChelle Meister
|
Rough-in | 11/14/2006 | 11/15/2006 | 11/15/2006 | A | PART |
Alan Hauser
|
|
|
walked auditorium area
|
Rough-in | 11/3/2006 | 11/8/2006 | 11/8/2006 | A | NR |
Alan Hauser
|
|
|
Please contact job foreman, Ken Sereduk - ###-####. Internet Inspection Request from: RaChelle Meister
|
Rough-in | 10/27/2006 | 11/1/2006 | 11/1/2006 | A | PART |
Alan Hauser
|
|
|
no work to look at this week
|
Rough-in | 10/18/2006 | 10/25/2006 | 10/25/2006 | A | PART |
Alan Hauser
|
|
|
Please contact project manager, Ted Frisbee, Jr - ###-####. Internet Inspection Request from: RaChelle Meister
|
Rough-in | 10/11/2006 | 10/18/2006 | 10/18/2006 | A | PART |
Alan Hauser
|
|
|
pharmacy area ok and areas between surgury rooms
|
Rough-in | 10/9/2006 | 10/11/2006 | 10/11/2006 | A | PART |
Alan Hauser
|
|
|
Please contact project manager, Ted Frisbee, Jr. - ###-####. Internet Inspection Request from: RaChelle Meister
|
Rough-in | 9/28/2006 | 10/4/2006 | 10/4/2006 | A | PART |
Alan Hauser
|
|
|
pharmacy ok for tile, except in area around flue pipe from sterlizer
|
Rough-in | 9/26/2006 | 9/27/2006 | 9/27/2006 | A | CANC |
Troy James
|
|
|
Please contact project manager, Ted Frisbee, Jr. - ###-####. Internet Inspection Request from: RaChelle Meister no inspection neccessary today, can wait till next wednesday when allen is back per ted frisbee
|
Rough-in | 9/19/2006 | 9/20/2006 | 9/20/2006 | A | PART |
Alan Hauser
|
|
|
no new work
|
Mec-Request for Extension | 9/13/2006 | 9/13/2006 | 9/13/2006 | P | PASS |
Alan Hauser
|
|
|
Please contact pro ject manager, Ted Frisbee, Jr. - ###-####. Internet Inspection Request from: RaChelle Meister
|
Rough-in | 9/5/2006 | 9/6/2006 | 9/6/2006 | A | PART |
Alan Hauser
|
|
|
nothing, went over and signed temp. occ. for fmc
|
Conference | 8/31/2006 | 9/6/2006 | 9/5/2006 | A | CANC |
Alan Hauser
|
|
|
Please contact project supervisor - Ted Frisbee, Jr. - ###-####. Internet Inspection Request from: RaChelle Meister Inspection cancelled from web by: RaChelle Meister
|
Rough-in | 9/5/2006 | 9/6/2006 | 9/5/2006 | A | CANC |
Alan Hauser
|
|
|
Please contact project manager, Ted Frisbee Jr - ###-####. Internet Inspection Request from: RaChelle Meister Inspection cancelled from web by: RaChelle Meister
|
Rough-in | 8/17/2006 | 8/23/2006 | 8/23/2006 | A | PART |
Alan Hauser
|
|
|
no work to look at today
|
Rough-in | 8/11/2006 | 8/16/2006 | 8/16/2006 | A | PART |
Alan Hauser
|
|
|
Please contact project supervisor, Ted Frisbee Jr - ###-####. Internet Inspection Request from: RaChelle Meister
|
Rough-in | 8/2/2006 | 8/9/2006 | 8/9/2006 | A | PART |
Alan Hauser
|
|
|
10th and 3rd floor
|
Rough-in | 7/27/2006 | 8/2/2006 | 8/2/2006 | A | PART |
Alan Hauser
|
|
|
Please contact project supervisor, Ted Frisbee, Jr. - ###-####. Internet Inspection Request from: RaChelle Meister
|
Rough-in | 7/18/2006 | 7/19/2006 | 7/19/2006 | A | PART |
Alan Hauser
|
|
|
looked at plenums on 10 and surgery rooms on 2
|
Rough-in | 7/11/2006 | 7/12/2006 | 7/12/2006 | A | PART |
Alan Hauser
|
|
|
Please contact project supervisor, Ted Frisbee, Jr - ###-#### Internet Inspection Request from: RaChelle Meister
|
Rough-in | 6/26/2006 | 6/28/2006 | 6/28/2006 | A | PART |
Alan Hauser
|
|
|
Please contact job foreman, Rich Scown - ###-####. Internet Inspection Request from: RaChelle Meister
|
Rough-in | 6/20/2006 | 6/21/2006 | 6/21/2006 | A | PASS |
Alan Hauser
|
|
|
Please contact project manager, Ted Frisbee, Jr. - ###-####. Internet Inspection Request from: RaChelle Meister
|
Rough-in | 6/6/2006 | 6/7/2006 | 6/7/2006 | A | PART |
Alan Hauser
|
|
|
Please contact project manager, Ted Frisbee, Jr. - ###-####. Internet Inspection Request from: RaChelle Meister
|
Rough-in | 5/25/2006 | 5/31/2006 | 5/31/2006 | A | PART |
Alan Hauser
|
|
|
taps and s/f dampers ok at shaft on 5th floor
|
Rough-in | 5/22/2006 | 5/24/2006 | 5/24/2006 | A | PART |
Alan Hauser
|
|
|
walked fmc and surgery floor with rich
|
Rough-in | 5/17/2006 | 5/18/2006 | 5/18/2006 | A | PART |
Alan Hauser
|
|
|
do early am, couldn't get to this on wednesday because of so many other inspections. talk to ted jr. about damper changes in cancer care
|
Rough-in | 5/10/2006 | 5/17/2006 | 5/17/2006 | A | PART |
Alan Hauser
|
|
|
will do thursday morning am
|
Rough-in | 4/25/2006 | 4/26/2006 | 4/26/2006 | A | PART |
Alan Hauser
|
|
|
Please contact project manager, Ted Frisbee - ###-#### Internet Inspection Request from: RaChelle Meister
|
Rough-in | 4/10/2006 | 4/12/2006 | 4/12/2006 | A | PART |
Alan Hauser
|
|
|
duct ok
|
Rough-in | 3/29/2006 | 4/5/2006 | 4/5/2006 | A | PART |
Alan Hauser
|
|
|
went over most of the two buildings, no problems
|
Rough-in | 3/22/2006 | 3/29/2006 | 3/30/2006 | A | NR |
Alan Hauser
|
|
|
no answer to two calls
|
Final | 3/23/2006 | 3/24/2006 | 3/24/2006 | A | CANC |
Troy James
|
|
|
Rough-In and Final - Please contact job foreman, Carl Morris - ###-####. Internet Inspection Request from: RaChelle Meister Hobson office scheduled wrong job for inspection
|
Rough-in | 3/17/2006 | 3/22/2006 | 3/22/2006 | A | CANC |
Troy James
|
|
|
Please contact project manager, Ted Frisbee, Jr. - ###-####. Internet Inspection Request from: RaChelle Meister
|
Rough-in | 3/21/2006 | 3/22/2006 | 3/22/2006 | A | CANC |
Alan Hauser
|
|
|
Please contact project manager, Ted Frisbee, Jr. - ###-####. Internet Inspection Request from: RaChelle Meister Inspection cancelled from web by: RaChelle Meister
|
Rough-in | 3/10/2006 | 3/15/2006 | 3/15/2006 | A | PART |
Alan Hauser
|
|
|
went over entire tower, shaft lay out, and future location of dampers
|
Rough-in | 2/28/2006 | 2/28/2006 | 2/28/2006 | P | PART |
Troy James
|
|
|
walk through inspection basement, 1and 2 floors
|
Rough-in | 1/24/2006 | 1/24/2006 | 1/24/2006 | P | PART |
Troy James
|
|
|
rough duct inspection and framing of f/d
|
Rough-in | 1/23/2006 | 1/23/2006 | 1/23/2006 | A | PART |
Troy James
|
|
|
partial inspection of duct at basement and first level, no f/d or fsd installed at this time
|