Permit Information
Permit NumberMEC06-01844
StatusFinaled
Name A-1 HEATING & AIR CONDITIONING
Site Address 2398 E GOWEN RD
Project Name 
Customer Number3060603
ePlanReview 
Description
Mechanical Permit - Alteration: INSTALL 2 ROOF TOP UNITS/GAS PIPING TO 2 ROOF TOP UNITS AND WATER HEATER
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/12/20069/13/20069/13/2006APASS
DetailsTroy James
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS
Final9/12/20069/12/20069/12/2006PFAIL
DetailsTroy James
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS
VENTS FOR REGULATORS ARE REQUIRED TO HAVE TWO 90 DEGREE FITTINGS SO WATER CANNOT ENTER
Final9/9/20069/12/20069/12/2006AFAIL
DetailsTroy James
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS
vent gas regulators at rtu's 10' away or 2' above air intake
Final8/15/20068/16/20068/16/2006PFAIL
DetailsTroy James
KEY UNDER ROCK ON RIGHT HAND SIDE OF FRONT DOOR; Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS
mounting position incorrect for regulator, condensate drains not installed to rtu's, still no permanent ladder to actually get on roof
Final8/14/20068/15/20068/15/2006AFAIL
DetailsTroy James
KEY UNDER ROCK ON RIGHT HAND SIDE OF FRONT DOOR; Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS
c/n posted
Final8/11/20068/14/20068/14/2006AFAIL
DetailsTroy James
Phone #: ###-####
no access
Rough-in6/23/20066/23/20066/23/2006PPASS
DetailsTroy James
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS
Pressure Test6/22/20066/22/20066/22/2006PPASS
DetailsTroy James
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS
2lb system
Rough-in6/22/20066/22/20066/22/2006PFAIL
DetailsTroy James
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS
flue may need to be relocated and to be 8' from parapet or two feet above