Final | 8/3/2006 | 8/10/2006 | 8/10/2006 | P | FAIL |
Dixie Fellows
|
|
|
Phone #: ###-#### Internet Inspection Request from: loretta barck..flue has to slope back towards furnace a 1/4" per foot, wrap the flue in 1 1/2" armaflex in crawl, the condensate doesn't slope to the outside and water is sitting in the pipe instead of draining
|