Final | 1/26/2007 | 1/26/2007 | 1/26/2007 | P | PASS |
Alan Hauser
|
|
|
Phone #: ###-####
|
Final | 1/24/2007 | 1/25/2007 | 1/26/2007 | A | PASS |
Alan Hauser
|
|
|
Phone #: ###-####
|
Final | 1/23/2007 | 1/24/2007 | 1/24/2007 | A | PEND |
Dixie Fellows
|
|
|
Phone #: ###-####..called matt to reschedule..training classes this week and shorthanded..thanks
|
Final | 1/22/2007 | 1/23/2007 | 1/23/2007 | P | CANC |
Jim Johnson
|
|
|
Phone #: ###-#### Inspection cancelled from web by: Brent Lacy
|
MEC-Aging Inspection | 11/29/2006 | 11/29/2006 | 11/29/2006 | | CANC |
Alan Hauser
|
|
|
|
Pressure Test | 9/27/2006 | 9/28/2006 | 9/28/2006 | A | PART |
Bill VanDegrift
|
|
|
Phone #: ###-#### Internet Inspection Request from: Brent Lacy 20# gas test for fireplace from reg. in fire riser room ok.
|
Pressure Test | 9/26/2006 | 9/27/2006 | 9/27/2006 | A | FAIL |
Troy James
|
|
|
This is a gas inspection for the fire place in the main entry.; Phone #: ###-#### Internet Inspection Request from: Brent Lacy shutoff valve cannot be inaccessable above fireplace, guys on site don't know anything about where branch line ties to main and if tieing into 2# system.
|
Pressure Test | 8/25/2006 | 8/28/2006 | 8/28/2006 | A | PART |
Alan Hauser
|
|
|
20# test for furn. by stairways, and bbq
|
Pressure Test | 7/27/2006 | 7/28/2006 | 7/28/2006 | A | PART |
Alan Hauser
|
|
|
all piping on ground floor tested, all that is left is risers on each end to furn. on upper floors
|
Pressure Test | 7/6/2006 | 7/7/2006 | 7/7/2006 | A | PART |
Alan Hauser
|
|
|
60 pound test ok for lobby, pool room, and kitchen
|