Rough-in | 11/28/2007 | 11/28/2007 | 11/28/2007 | P | PASS |
Troy James
|
|
|
|
Final | 11/28/2007 | 11/28/2007 | 11/28/2007 | P | PASS |
Troy James
|
|
|
|
Final | 11/27/2007 | 11/27/2007 | 11/27/2007 | P | FAIL |
Troy James
|
|
|
fire dampers - corridors 1st floor Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen framing not completed at couple of fsd and grease duct needs to be extended and fire wrapped out of wall
|
Final | 11/6/2007 | 11/6/2007 | 11/6/2007 | A | FAIL |
Troy James
|
|
|
need some straps to flex duct and fix angles at fsd 6th floor
|
Final | 11/2/2007 | 11/2/2007 | 11/2/2007 | A | CANC |
Troy James
|
|
|
partial final - corridors only Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen need to reschedule for next week when travis can meet me on site
|
MEC-Aging Inspection | 10/1/2007 | 10/1/2007 | 10/1/2007 | | PASS |
Dixie Fellows
|
|
|
wip
|
MEC-Aging Inspection | 7/31/2007 | 7/31/2007 | 8/6/2007 | | PASS |
Dixie Fellows
|
|
|
wip
|
Rough-in | 5/30/2007 | 5/31/2007 | 5/31/2007 | A | PART |
Dixie Fellows
|
|
|
grease duct wrap...duct wrap complete.ok to cover
|
Rough-in | 5/29/2007 | 5/30/2007 | 5/30/2007 | A | PART |
Dixie Fellows
|
|
|
final inspection for grease duct Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen
|
Conference | 5/16/2007 | 5/17/2007 | 5/17/2007 | A | PASS |
Dixie Fellows
|
|
|
###-#### travis..will meet travis fri am to look at listings
|
Rough-in | 5/14/2007 | 5/16/2007 | 5/16/2007 | A | NR |
Dixie Fellows
|
|
|
Fire wrap - 2nd layer Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen..waiting on info about listing on wrap
|
Rough-in | 5/8/2007 | 5/9/2007 | 5/9/2007 | A | PART |
Dixie Fellows
|
|
|
grease duct inspect - first wrap of remaining duct Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen..ok to put 2nd layer of wrap floors 3-6
|
Rough-in | 4/30/2007 | 5/1/2007 | 5/1/2007 | A | PASS |
Dixie Fellows
|
|
|
grease duct inspection Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen
|
Rough-in | 4/13/2007 | 4/17/2007 | 4/17/2007 | A | PART |
Dixie Fellows
|
|
|
GREASE DUCT - 2ND LAYER Phone #: ###-####..need band on bottom section between 1st and 2nd floor..tape up loose ends
|
Rough-in | 4/11/2007 | 4/12/2007 | 4/12/2007 | A | PART |
Dixie Fellows
|
|
|
Grease Duct Inspection - 1st 20'' 1st layer Phone #: ###-####...1st layer of duct wrap in shaft ok
|
Rough-in | 4/4/2007 | 4/5/2007 | 4/5/2007 | A | PART |
Dixie Fellows
|
|
|
grease duct Phone #: ###-####---met with travis to discuss duct-wrapping part of the grease duct so they can build the shaft around it. ok to put on first layer, call for inspection and then install 2nd layer..dixie
|
Rough-in | 3/5/2007 | 3/6/2007 | 3/6/2007 | A | PEND |
Dixie Fellows
|
|
|
grease duct inspection Phone #: ###-####...1st access ok..waiting to find out if they are going to move them into the stairwell.
|
Rough-in | 2/22/2007 | 2/23/2007 | 2/23/2007 | A | PART |
Dixie Fellows
|
|
|
Rough-in /Travis Phone #: ###-####..partial grease duct inspection..travis will cut in the access doors and re-call and i will check the inside welds again at each opening
|
Conference | 2/21/2007 | 2/22/2007 | 2/22/2007 | A | PASS |
Dixie Fellows
|
|
|
Travis - Cover Phone #: ###-####..weekly check ok..travis will schedule a r/i for fri am and i will inspect some grease duct
|
Conference | 1/31/2007 | 2/1/2007 | 2/1/2007 | A | PASS |
Dixie Fellows
|
|
|
Weekly Confrence Rough in Corridor Phone #: ###-####..
|
Rough-in | 1/16/2007 | 1/17/2007 | 1/17/2007 | A | PART |
Dixie Fellows
|
|
|
Grease Duct Inspection Phone #: ###-####...looked at 4 sections of grease duct all ok
|
Conference | 1/16/2007 | 1/16/2007 | 1/16/2007 | P | PASS |
Dixie Fellows
|
|
|
Conference Phone #: ###-####..met with dave and travis along with forest (fire inspector and discussed fire protection) dave will call for grease duct inspection for wednesday
|
Conference | 1/9/2007 | 1/11/2007 | 1/11/2007 | A | PART |
Dixie Fellows
|
|
|
Conference w/ Dave Tully Phone #: ###-####..DAVE WILL RESCHEDULE AND WE WILL MEET WITH FOREST TUES AM 9:30
|