Final | 4/5/2007 | 4/5/2007 | 4/5/2007 | P | PASS |
Troy James
|
|
|
|
Rough-in | 4/4/2007 | 4/5/2007 | 4/5/2007 | A | PASS |
Troy James
|
|
|
jamie; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
Rough-in | 4/2/2007 | 4/3/2007 | 4/3/2007 | A | FAIL |
Troy James
|
|
|
jaime - correction, pls call for key location; Phone #: ###-#### Internet Inspection Request from: Victoria Beall chimney liner cannot be exposed and connected to furnace, verify flexible duct approved for use
|
Pressure Test | 3/26/2007 | 3/26/2007 | 3/26/2007 | P | FAIL |
Bill VanDegrift
|
|
|
jaimie - pls call for entrane; Phone #: ###-#### Internet Inspection Request from: Victoria Beall two cumbustion air openings, one high and one low, 100 sq. in. each, required into furnace closet. combustable foam sealant is not permitted to be installed around furnace flue. 20# test ok.
|