Information based on query as of Tuesday, July 2, 2024.
Permit Information
Permit NumberMEC07-01380
StatusFinaled
Name BARGREEN-ELLINGSON INC
Site Address 5850 N FIVE MILE RD
Project NameBONAVENTURE PLACE
Customer Number 
ePlanReview 
Description
Type I Exhaust hood, duct, fan, Type II vapor dishwashing hood, fan (no duct) Mua by owners // initial value $12,609 ///Final value is $18,428//4/8/08 LEG
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/31/20078/31/20078/31/2007PPASS
DetailsAlan Hauser
Rough-in7/24/20077/25/20077/25/2007PPASS
DetailsAlan Hauser
class 1 hood and grease duct approved, placed green tag on front of hood
Rough-in7/20/20077/24/20077/23/2007ANR
DetailsAlan Hauser
Rough-in7/19/20077/20/20077/20/2007APART
DetailsAlan Hauser
went over items to complete on grease duct, no hood at this time
Rough-in7/10/20077/11/20077/11/2007APART
DetailsAlan Hauser
first wrap of duct wrap ok
Rough-in6/11/20076/11/20076/11/2007PFAIL
DetailsAlan Hauser
time to write and deliever correction notice about class 1 hood and grease duct
Rough-in6/5/20076/6/20076/6/2007AFAIL
DetailsAlan Hauser
any grease duct wrap used in boise, has to be tested to ac 101, there are products that have been, and all require two layers of wrap.
Rough-in6/4/20076/5/20076/5/2007APART
DetailsAlan Hauser
stopped and picked up new information on 3m grease duct wrap
Conference5/14/20075/14/20075/14/2007PPART
DetailsLee Rice
Scheduled by a contractor via Hello! on 5/14/2007 at 10:12:44 AM. Contact: ###-####. inspected grease duct welds on class I kittchen exhaust. Duct liying on deck to be insulated and intalled then reispect tie in joints at that time..