Final | 8/31/2007 | 8/31/2007 | 8/31/2007 | P | PASS |
Alan Hauser
|
|
|
|
Rough-in | 7/24/2007 | 7/25/2007 | 7/25/2007 | P | PASS |
Alan Hauser
|
|
|
class 1 hood and grease duct approved, placed green tag on front of hood
|
Rough-in | 7/20/2007 | 7/24/2007 | 7/23/2007 | A | NR |
Alan Hauser
|
|
|
|
Rough-in | 7/19/2007 | 7/20/2007 | 7/20/2007 | A | PART |
Alan Hauser
|
|
|
went over items to complete on grease duct, no hood at this time
|
Rough-in | 7/10/2007 | 7/11/2007 | 7/11/2007 | A | PART |
Alan Hauser
|
|
|
first wrap of duct wrap ok
|
Rough-in | 6/11/2007 | 6/11/2007 | 6/11/2007 | P | FAIL |
Alan Hauser
|
|
|
time to write and deliever correction notice about class 1 hood and grease duct
|
Rough-in | 6/5/2007 | 6/6/2007 | 6/6/2007 | A | FAIL |
Alan Hauser
|
|
|
any grease duct wrap used in boise, has to be tested to ac 101, there are products that have been, and all require two layers of wrap.
|
Rough-in | 6/4/2007 | 6/5/2007 | 6/5/2007 | A | PART |
Alan Hauser
|
|
|
stopped and picked up new information on 3m grease duct wrap
|
Conference | 5/14/2007 | 5/14/2007 | 5/14/2007 | P | PART |
Lee Rice
|
|
|
Scheduled by a contractor via Hello! on 5/14/2007 at 10:12:44 AM. Contact: ###-####. inspected grease duct welds on class I kittchen exhaust. Duct liying on deck to be insulated and intalled then reispect tie in joints at that time..
|