Final | 3/14/2008 | 3/14/2008 | 3/14/2008 | P | PASS |
Troy James
|
|
|
Phone #: ###-#### Internet Inspection Request from: Scott Wickstrom
|
Final | 3/13/2008 | 3/13/2008 | 3/13/2008 | P | FAIL |
Troy James
|
|
|
Phone #: ###-#### Internet Inspection Request from: Scott Wickstrom venting for gas regulators installed incorrectly
|
Final | 3/7/2008 | 3/7/2008 | 3/7/2008 | A | FAIL |
Troy James
|
|
|
gas regulators are required to be mounted horizontally and upright, install sediment trap after valve and before regulator, complete connection to pool heater
|
Pressure Test | 11/2/2007 | 11/2/2007 | 11/2/2007 | P | PASS |
Troy James
|
|
|
I need to add 2 fixtures. A water heater and a furnace. Thank you Helen Phone #: ###-#### Internet Inspection Request from: Scott Wickstrom 20# ok, left c/n for vent limiter regs to be checked at final
|
Final | 8/29/2007 | 8/29/2007 | 8/29/2007 | P | PASS |
Bill VanDegrift
|
|
|
Phone #: ###-#### Internet Inspection Request from: Scott Wickstrom
|
Rough-in | 8/27/2007 | 8/27/2007 | 8/27/2007 | P | FAIL |
Dixie Fellows
|
|
|
Phone #: ###-#### Internet Inspection Request from: Scott Wickstrom...need to fill in trench under gas line with sand or dirt.
|
Pressure Test | 7/13/2007 | 7/13/2007 | 7/13/2007 | P | PASS |
Dixie Fellows
|
|
|
Phone #: ###-#### Internet Inspection Request from: Scott Wickstrom..60lb u/g test to future new bldg ok
|
Pressure Test | 7/2/2007 | 7/2/2007 | 7/2/2007 | P | PART |
Dixie Fellows
|
|
|
Phone #: ###-#### Internet Inspection Request from: Scott Wickstrom...60lb u/g gas from meter in trench to other side of house ok
|