Final | 9/4/2007 | 9/4/2007 | 9/4/2007 | P | PASS |
Alan Hauser
|
|
|
|
Pressure Test | 9/4/2007 | 9/4/2007 | 9/4/2007 | P | PASS |
Alan Hauser
|
|
|
20#
|
Final | 8/21/2007 | 8/24/2007 | 8/24/2007 | P | FAIL |
Alan Hauser
|
|
|
pressure test has failed again, gauge on 5#. soap out piping and fix leak.
|
Final | 8/8/2007 | 8/9/2007 | 8/9/2007 | A | FAIL |
Alan Hauser
|
|
|
gas piping can not be under strain, remove tee and plug at floor to remove strain on piping. isolate piping from concrete floor
|
Final | 8/6/2007 | 8/7/2007 | 8/7/2007 | P | FAIL |
Alan Hauser
|
|
|
Jim Magee - contact person Phone #: ###-#### pressure test failed and talked to jim about fixing gas pipe, where it turns up to furn., so won't touch floor
|