Final | 6/4/2008 | 6/4/2008 | 6/4/2008 | P | PASS |
Troy James
|
|
|
Final reinspect Phone #: ###-#### Internet Inspection Request from: Nicole Pulley
|
Final | 5/14/2008 | 5/14/2008 | 5/14/2008 | P | FAIL |
Troy James
|
|
|
Please do final mechanical inspection Phone #: ###-#### Internet Inspection Request from: Nicole Pulley gas shutoff shall be before union at w/h, protection post at furnace
|
Rough-in | 10/15/2007 | 10/16/2007 | 10/16/2007 | A | PASS |
Troy James
|
|
|
Need a rough in reinspect and a gas pressure test. Please. Phone #: ###-#### Internet Inspection Request from: Nicole Pulley 20# test
|
Conference | 10/3/2007 | 10/4/2007 | 10/4/2007 | A | DONE |
Troy James
|
|
|
Please call when heading that way so we may meet you there. Phone #: ###-#### Internet Inspection Request from: Nicole Pulley informed contractor to relocate tankless water heater from exterior wall
|
Conference | 10/3/2007 | 10/4/2007 | 10/3/2007 | A | CANC |
Troy James
|
|
|
Phone #: ###-#### Internet Inspection Request from: Nicole Pulley Inspection cancelled from web by: Nicole Pulley
|
Rough-in | 10/1/2007 | 10/1/2007 | 10/1/2007 | A | FAIL |
Troy James
|
|
|
gas test failed, 1" gas line to w/h and furnace is undersized, see clearance requirements for w/h on exterior from openable windows, attach mechanical permit to building permit
|