DOC - Permit Finaled | 10/17/2007 | 10/17/2007 | 10/17/2007 | P | PASS |
Dixie Fellows
|
|
|
joe ###-####
|
Final | 10/16/2007 | 10/17/2007 | 10/17/2007 | A | FAIL |
Dixie Fellows
|
|
|
Call Joe please...........Gas test Phone #: ###-#### Internet Inspection Request from: joe paige...the information for this permit is listed under the pressure test request...no gas inspection done as the equipment was illegal for this type of installation...int gas (kurt) is aware of the problems
|
Pressure Test | 10/17/2007 | 10/17/2007 | 10/17/2007 | P | FAIL |
Dixie Fellows
|
|
|
joe ###-####....the unvented gas units the owner purchased to install in the dog grooming business are not listed for this installation. there is not enough volume in the rooms for combustion air and these are unvented..i called int gas to make sure no meter was set at this address unless the owner changed the units...kurt with int gas is aware of the problems and was unable to find this address in the grid maps.
|
Final | 10/16/2007 | 10/16/2007 | 10/16/2007 | P | FAIL |
Dixie Fellows
|
|
|
Call Mark please Phone #: ###-#### Internet Inspection Request from: joe paige.this permit not attached to building permit on line
|