Final | 4/24/2008 | 4/25/2008 | 4/25/2008 | A | PASS |
Dixie Fellows
|
|
|
Phone #: ###-#### Internet Inspection Request from: misty evans....signed perm occupancy
|
Final | 4/22/2008 | 4/23/2008 | 4/23/2008 | A | PART |
Dixie Fellows
|
|
|
Phone #: ###-#### Internet Inspection Request from: misty evans....temp occupancy ok...waiting on air balance report
|
Final | 4/18/2008 | 4/21/2008 | 4/21/2008 | A | CANC |
Dixie Fellows
|
|
|
Phone #: ###-#### Internet Inspection Request from: misty evans...remove screws from angle to structure...need air balance report
|
Final | 4/16/2008 | 4/17/2008 | 4/17/2008 | A | NR |
Dixie Fellows
|
|
|
Phone #: ###-#### Internet Inspection Request from: misty evans...
|
Rough-in | 4/10/2008 | 4/11/2008 | 4/11/2008 | A | PASS |
Troy James
|
|
|
Need Troy to ispect grease duct fire wrap on the roof. Call Russ @ ###-#### Phone #: ###-#### Internet Inspection Request from: misty evans ok to cover duct shaft at roof
|
Rough-in | 4/9/2008 | 4/10/2008 | 4/10/2008 | A | PART |
Dixie Fellows
|
|
|
Any questions call Russ @ ###-#### Phone #: ###-#### Internet Inspection Request from: misty evans...ok to cover lids in lounge, kitchen and bath halls
|
Rough-in | 4/2/2008 | 4/3/2008 | 4/3/2008 | A | PART |
Troy James
|
|
|
Need Troy to inspect grease duct at Bonefish Grill. Call Russ ###-#### if you have any questions. Thank you. Phone #: ###-#### Internet Inspection Request from: misty evans ok to fire wrap grease duct up to top of shaft
|
Rough-in | 4/1/2008 | 4/2/2008 | 4/2/2008 | A | PART |
Dixie Fellows
|
|
|
Need inspection on grease duct that is now installed and grease duct that has been wrapped. Any questions call Russ ###-#### Phone #: ###-#### Internet Inspection Request from: misty evans...inside welds ok off 2nd hood in back..can go ahead with fire wrap
|
Rough-in | 3/27/2008 | 3/28/2008 | 3/28/2008 | A | PART |
Dixie Fellows
|
|
|
Need 2nd grease duct firewrap inspection. Inspection is needed before 11:00. Call Russ with any questions ###-####. Phone #: ###-#### Internet Inspection Request from: misty evans...2nd wrap ok on 2nd hood
|
Rough-in | 3/26/2008 | 3/27/2008 | 3/27/2008 | A | PART |
Dixie Fellows
|
|
|
CHECK C/N FOR LOW SPOT IN HORIZ. SECTION OF GREASE DUCT...low spot ok..can go ahead and put on fire wrap
|
Rough-in | 3/26/2008 | 3/26/2008 | 3/26/2008 | P | PASS |
Troy James
|
|
|
this is the check the 1st layer of fire wrap on vertical section of grease duct for hood #2
|
Rough-in | 3/26/2008 | 3/26/2008 | 3/26/2008 | P | PART |
Dixie Fellows
|
|
|
Need inspection of corrections on grease duct at Bonefish Grill. Also need inspection of 1st fire wrap on grease duct at shop. see dixie. Contact Russ with any questions. ###-#### Phone #: ###-#### Internet Inspection Request from: misty evans...troy will check 1st layer of fire wrap this pm and i will check correction on grease duct thurs am..i rescheduled this already..dixie
|
Rough-in | 3/26/2008 | 3/26/2008 | 3/26/2008 | P | CANC |
Dixie Fellows
|
|
|
Need inspection of corrections on existing grease duct. Phone #: ###-#### Internet Inspection Request from: misty evans Inspection cancelled from web by: misty evans
|
Conference | 3/25/2008 | 3/25/2008 | 3/25/2008 | P | PART |
Dixie Fellows
|
|
|
Need Dixie to inspect Grease duct at 1:00PM Please call Russ - ###-#### Phone #: ###-#### Internet Inspection Request from: misty evans...welds on vertical section of 2nd hood ok
|
Rough-in | 3/13/2008 | 3/14/2008 | 3/14/2008 | A | FAIL |
Dixie Fellows
|
|
|
Dixie please inspect the grease duct. Call Brent if need to at above number, Thank you Phone #: ###-#### Internet Inspection Request from: misty evans...need to grind down overlap and there is a bow is the 90' portion of horizontal run in grease duct
|
Rough-in | 3/7/2008 | 3/10/2008 | 3/10/2008 | A | PART |
Dixie Fellows
|
|
|
Need Dixie to inspect grease ducts mon a.m. before dropping them thru chase. 9:00 would be great. Thanks Phone #: ###-#### Internet Inspection Request from: misty evans...welds on vertical duct ok...fire wrap as well
|
Rough-in | 2/29/2008 | 3/3/2008 | 3/3/2008 | A | PART |
Dixie Fellows
|
|
|
reuben ###-#### call when at job site...OK TO COVER HARD LID IN BATHROOM
|
Rough-in | 2/29/2008 | 2/29/2008 | 2/29/2008 | P | PART |
Dixie Fellows
|
|
|
Need dixie to inspect hoods again. Thank you. Phone #: ###-#### Internet Inspection Request from: misty evans...will check sprinkler head in grease duct and top of duct on monday
|
Rough-in | 2/27/2008 | 2/28/2008 | 2/28/2008 | A | PASS |
Dixie Fellows
|
|
|
Need dixie to inspect 2nd layer of fire wrap as soon as possible. thank you Phone #: ###-#### Internet Inspection Request from: misty evans
|
Rough-in | 2/27/2008 | 2/27/2008 | 2/27/2008 | A | PART |
Dixie Fellows
|
|
|
###-#### - brett Note: firewrap on the hood - if possible around 9:00 am...1st layer of wrap on type 1 hood ok
|
Rough-in | 2/25/2008 | 2/25/2008 | 2/25/2008 | P | NR |
Dixie Fellows
|
|
|
This is the 2nd inspection for fire wrap per dixie''s request during conference. Phone #: ###-#### Internet Inspection Request from: misty evans...WAITING ON SPRINKLER CONTRACTOR
|
Rough-in | 2/25/2008 | 2/25/2008 | 2/25/2008 | P | PART |
Dixie Fellows
|
|
|
brent ###-#### check welds on grease duct at hoods only (2)
|
Conference | 2/22/2008 | 2/25/2008 | 2/25/2008 | A | PASS |
Dixie Fellows
|
|
|
Brent would like to meet Dixie at 9:00am on the jobsite. Phone #: ###-#### Internet Inspection Request from: misty evans..discussed fire-wrap and clearances on roof..i will have troy verify once brent has it layed out.
|
Rough-in | 2/22/2008 | 2/22/2008 | 2/22/2008 | P | NR |
Dixie Fellows
|
|
|
henry - welding behind hood Phone #: ###-####
|
Conference | 2/21/2008 | 2/21/2008 | 2/21/2008 | A | PASS |
Dixie Fellows
|
|
|
|
Conference | 2/19/2008 | 2/20/2008 | 2/19/2008 | A | CANC |
Dixie Fellows
|
|
|
Brent Evans would like to meet with Dixie Fellows at 11:00 AM. Please call number above to confirm with Brent. Phone #: ###-#### Internet Inspection Request from: misty evans Inspection cancelled from web by: misty evans
|