Final | 9/24/2008 | 9/25/2008 | 9/25/2008 | A | PASS |
Troy James
|
|
|
Gas flex is fixed! Thanks! Phone #: ###-#### Internet Inspection Request from: Brian Donahue
|
Final | 9/24/2008 | 9/24/2008 | 9/24/2008 | P | FAIL |
Troy James
|
|
|
Gas regulators have been completed per inspector. Call Darren for any questions. Thank you! Phone #: ###-#### Internet Inspection Request from: Brian Donahue gas flex connector undersized, inlet is 1"
|
Final | 9/23/2008 | 9/23/2008 | 9/23/2008 | P | FAIL |
Troy James
|
|
|
Please call Matt if you have any questions! Phone #: ###-#### Internet Inspection Request from: Brian Donahue need first stage regs to mau units, install sediment trap after gas valve to unit on roof
|
Rough-in | 8/29/2008 | 9/2/2008 | 9/2/2008 | A | PASS |
Troy James
|
|
|
ok to cover ceiling at offices only
|
Rough-in | 8/29/2008 | 8/29/2008 | 8/29/2008 | P | FAIL |
Troy James
|
|
|
This is a partial rough-in in office areas for cieling tile installation. Phone #: ###-#### Internet Inspection Request from: Brian Donahue need approved duct tape, install duct tape to inner liner
|
Pressure Test | 8/15/2008 | 8/15/2008 | 8/15/2008 | P | PASS |
Troy James
|
|
|
This is for a final gas pressure test. Please call Darren if you have any questions! Phone #: ###-#### Internet Inspection Request from: Brian Donahue 60# test
|
Rough-in | 8/15/2008 | 8/15/2008 | 8/15/2008 | A | PASS |
Troy James
|
|
|
This is a partial rough for sheetrock cover. Please call Matt if you have any questions! Thank you! Phone #: ###-#### Internet Inspection Request from: Brian Donahue ok to cover hard lids
|