DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/5/20101/6/20101/6/2010PPASS
DetailsTroy James
HOMEOWNER ###-#### Phone #: ###-#### Internet Inspection Request from: Bill Burch
Final1/4/20101/5/20101/5/2010PFAIL
DetailsTroy James
HOMEOWNER ###-#### FURNACE IN CRAWLSPACE Phone #: ###-#### Internet Inspection Request from: Bill Burch
flue connector cannot be in crawl space, flue shall not dip or sag and be installed upward, flue shall be b-vent in unconditioned space and need to lower condensate pump so condensate can drain with grade to pump