Final | 9/7/2010 | 9/7/2010 | 9/7/2010 | A | PASS |
Troy James
|
|
|
|
Rough-in | 7/16/2010 | 7/16/2010 | 7/16/2010 | P | PASS |
Troy James
|
|
|
ok rough for ceiling cover and fsd installation per manufacturer
|
Rough-in | 7/15/2010 | 7/16/2010 | 7/16/2010 | A | FAIL |
Troy James
|
|
|
jerry ###-####...unable to get a hold of jerry..need another contact name and # left notice to not cover ceiling at storage and adjacent room, fsd installation suppose to be on site
|
Rough-in | 7/14/2010 | 7/15/2010 | 7/15/2010 | P | PEND |
Dixie Fellows
|
|
|
inspect hard lids and reinspect fsd..unable to get a hold of jerry..i rescheduled this for fri am...need another name and #
|
Rough-in | 7/14/2010 | 7/14/2010 | 7/14/2010 | P | CANC |
Troy James
|
|
|
inspect hard lid for cover and reinspect fsd
|
Final | 7/14/2010 | 7/14/2010 | 7/14/2010 | P | FAIL |
Troy James
|
|
|
Please call Jerry Merrit @ ###-#### if you have any questions Phone #: ###-#### >> Inspection requested via web by Angie maguire fire smoke dampers installed incorrectly, remove angle from under sheetrock, provide expansion gap and reinstall angles per manufancturer
|