Final | 4/1/2011 | 4/4/2011 | 4/4/2011 | A | PASS |
Alan Hauser
|
|
|
|
Final | 3/31/2011 | 4/1/2011 | 4/1/2011 | A | PEND |
Dixie Fellows
|
|
|
for installation issues, call Eric @ ###-#### Phone #: ###-#### >> Inspection requested via web by Angie maguire..re-sent to alan for monday
|
Final | 3/25/2011 | 3/29/2011 | 3/29/2011 | A | FAIL |
Alan Hauser
|
|
|
this gas line system has the wrong mp regulators. for some reason this is a 5# system, which requires mp regulators with the over pressure protection built in to regulator
|
Final | 3/3/2011 | 3/7/2011 | 3/7/2011 | A | NR |
Alan Hauser
|
|
|
recall for final when unit heaters are hooked up to gasline, 60# test ok on gasline, ok to set meter
|
Pressure Test | 3/7/2011 | 3/7/2011 | 3/7/2011 | A | PASS |
Alan Hauser
|
|
|
60#
|
Pressure Test | 2/22/2011 | 2/23/2011 | 2/23/2011 | A | PEND |
Dixie Fellows
|
|
|
please call Dave @ ###-#### with any installation issues. Phone #: ###-#### >> Inspection requested via web by Angie maguire
|
Rough-in | 2/22/2011 | 2/23/2011 | 2/23/2011 | A | PART |
Dixie Fellows
|
|
|
please call Dave @ ###-#### with any installation issues. Phone #: ###-#### >> Inspection requested via web by Angie maguire...need occupancy permit and specs for unit heaters
|