Final | 8/3/2011 | 8/4/2011 | 8/4/2011 | A | PASS |
Alan Hauser
|
|
|
|
Final | 8/3/2011 | 8/3/2011 | 8/4/2011 | P | PASS |
Alan Hauser
|
|
|
couldn't find card, alan was with kohls people some where
|
Rough-in | 7/6/2011 | 7/7/2011 | 7/7/2011 | A | PASS |
Alan Hauser
|
|
|
all grid ceiling areas ok for cover
|
Rough-in | 6/17/2011 | 6/17/2011 | 6/17/2011 | P | PART |
Alan Hauser
|
|
|
Ceiling Inspection on 2nd floor for sales are and areas that have grid in them. Phone #: ###-#### >> Inspection requested via web by Kirk Johns
|
Rough-in | 6/10/2011 | 6/13/2011 | 6/13/2011 | A | PART |
Alan Hauser
|
|
|
hard ceiling areas ok for cover
|
Conference | 6/3/2011 | 6/3/2011 | 6/3/2011 | P | PASS |
Alan Hauser
|
|
|
need opion on unit heater venting into loading dock wrote c/n that manufacture wants heater vented to the outdoors, not into the loading dock bays
|
Rough-in | 6/3/2011 | 6/3/2011 | 6/3/2011 | A | PART |
Alan Hauser
|
|
|
all fire dampers installed as per manufacture instructions, ok for cover
|
Rough-in | 5/28/2011 | 5/31/2011 | 5/31/2011 | A | FAIL |
Alan Hauser
|
|
|
fire damper installation guide not on site
|
Rough-in | 5/23/2011 | 5/24/2011 | 5/24/2011 | A | FAIL |
Troy James
|
|
|
ducts ok at second and first floor, need fire damper installation instructions and need the fire dampers installed in floor
|
Rough-in | 5/23/2011 | 5/23/2011 | 5/23/2011 | P | CANC |
Troy James
|
|
|
Partial Rough-in inspection for first floor heating at Kohls. Any questions, please contact Andrew at ###-#### Phone #: ###-#### >> Inspection requested via web by Kirk Johns rescheduled with andrew
|
Rough-in | 4/27/2011 | 4/28/2011 | 4/28/2011 | A | PART |
Alan Hauser
|
|
|
2nd floor duct sealed and insulated, ready for grid
|
Rough-in | 4/14/2011 | 4/14/2011 | 4/14/2011 | P | PART |
Alan Hauser
|
|
|
gas line holding pressure 60# test just starting duct installation
|