ePlanReviewNo
Description
Mechanical Permit - New: two gas furnace/two ac/ductwork/venting/gas piping
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/31/201111/1/201111/1/2011APASS
DetailsBill VanDegrift
air balance was done Monday Phone #: ###-#### >> Inspection requested via web by April Sims
Final10/24/201110/25/201110/25/2011PCANC
DetailsDixie Fellows
Phone #: ###-#### >> Inspection requested via web by April Sims Inspection cancelled from web by: April Sims
Final10/21/201110/24/201110/24/2011PCANC
DetailsDixie Fellows
Phone #: ###-#### >> Inspection requested via web by April Sims Inspection cancelled from web by: April Sims
Final10/18/201110/19/201110/19/2011PCANC
DetailsBill VanDegrift
As late as possible in the afternoon please. Air balancing to start about noon. Thanks, April. Phone #: ###-#### >> Inspection requested via web by April Sims Inspection cancelled from web by: April Sims
Mec-Aging Inspection9/8/20119/8/20119/9/2011 PASS
DetailsDixie Fellows
wip
Rough-in6/9/20116/10/20116/9/2011APASS
DetailsDixie Fellows
Dixie for Thursday afternoon. Phone #: ###-#### >> Inspection requested via web by April Sims...duct blaster test passed and document on furnace
Rough-in6/1/20116/1/20116/1/2011PPASS
DetailsBill VanDegrift
ri 60# test ok needs duct blaster test
Pressure Test5/31/20116/1/20116/1/2011ANR
DetailsDixie Fellows
Phone #: ###-#### >> Inspection requested via web by April Sims....waiting for manual j paper work
Rough-in5/31/20116/1/20116/1/2011ANR
DetailsDixie Fellows
Phone #: ###-#### >> Inspection requested via web by April Sims
Pressure Test5/27/20115/31/20115/31/2011ANR
DetailsAlan Hauser
will do when ready for hvac rough-in
Rough-in5/27/20115/31/20115/31/2011AFAIL
DetailsAlan Hauser
need correct approved wrightsoft report
the one on site was submitted and approved for western heating