Final | 11/11/2011 | 11/14/2011 | 11/14/2011 | A | PASS |
Bill VanDegrift
|
|
|
Phone #: ###-#### >> Inspection requested via web by Dustin Rich
|
Final | 10/11/2011 | 10/11/2011 | 10/11/2011 | P | NR |
Dixie Fellows
|
|
|
Phone #: ###-#### >> Inspection requested via web by Dustin Rich...need the air balance done
|
Rough-in | 9/2/2011 | 9/6/2011 | 9/6/2011 | A | PASS |
Troy James
|
|
|
Troy already inspected this I just had to call it in Phone #: ###-#### >> Inspection requested via web by Dustin Rich
|
Rough-in | 9/6/2011 | 9/6/2011 | 9/6/2011 | P | PASS |
Troy James
|
|
|
please have ther for 12:30 duct blasts >> Inspection requested via web by Dustin Rich
|
Rough-in | 9/2/2011 | 9/2/2011 | 9/2/2011 | P | FAIL |
Troy James
|
|
|
balanced dampers not installed, ok to install balance dampers at boot, need to retest duct seal, need to install nail plates at dryer and flue
|
Rough-in | 8/24/2011 | 8/25/2011 | 8/25/2011 | A | FAIL |
Dixie Fellows
|
|
|
Chance will be doing the duct blaster this morning. He will be ready at noon for a witness. His number is ###-#### Phone #: ###-#### >> Inspection requested via web by Dustin Rich..manual J doesn't match job
|